{"id":29589,"date":"2026-11-23T12:48:43","date_gmt":"2026-11-23T09:48:43","guid":{"rendered":"https:\/\/azeidkgroup.com\/sa\/media-center\/"},"modified":"2026-11-23T12:48:44","modified_gmt":"2026-11-23T09:48:44","slug":"foam-bladder-tank-brands-comparison","status":"publish","type":"post","link":"https:\/\/azeidkgroup.com\/en\/sa\/media-center\/foam-bladder-tank-brands-comparison\/","title":{"rendered":"Foam Bladder Tank Comparison: WATEX, FIRETECH, Falcon Gold and SFFECO by Approval, Capacity and Pressure"},"content":{"rendered":"\t\t<div data-elementor-type=\"wp-post\" data-elementor-id=\"29589\" class=\"elementor elementor-29589 elementor-29588 elementor-bc-flex-widget\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-3abefc2 e-con-full az-el-article e-flex e-con e-parent\" data-id=\"3abefc2\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-6283f4a elementor-widget elementor-widget-text-editor\" data-id=\"6283f4a\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-intro\">When a Saudi project needs a <strong>foam bladder tank<\/strong>, the question that usually follows is which brand to specify. AZEIDK supplies four: WATEX, FIRETECH, Falcon Gold and SFFECO. This comparison puts their published data side by side (approval, capacity range, working pressure, vessel and bladder materials, options) so the choice follows the project specification rather than the name on the tank.<\/p>\n<p>If you first need the basics of how a bladder tank works and how it is sized, start with our guide to <a href=\"\/en\/sa\/media-center\/foam-proportioning-bladder-tank\/\">foam proportioning and bladder tanks<\/a>, then come back here. All four tanks sit within AZEIDK&#8217;s <a href=\"\/en\/sa\/solutions\/special-fire-suppression-systems\/\">special fire suppression systems<\/a> scope.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-eb0bbc3 elementor-widget elementor-widget-text-editor\" data-id=\"eb0bbc3\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-keybox\"><h2>Key points<\/h2><ul><li>WATEX and FIRETECH: bladder tanks with a ratio controller, UL listed under Proportioners, Foam Concentrate, with the UL file numbers published on the product pages.<\/li><li>FIRETECH publishes the widest capacity range (100 to 20,000 L), a flow range of 75 to 36,000 L\/min and a twin-vessel (main and reserve) option.<\/li><li>Falcon Gold: roughly 189 to 12,000 L at 175 psi with a long options list; the product page does not quote a UL listing, so ask for approval documents if the specification requires one.<\/li><li>SFFECO: models SFD-U2 to SFD-U8-BTRFC, vertical and horizontal; capacity and pressure come from the model datasheet at quotation stage.<\/li><li>All four work the same way: fire water pressure squeezes the bladder and pushes concentrate to the ratio controller, with no foam pump and no power supply.<\/li><\/ul><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-2aeb82a elementor-widget elementor-widget-text-editor\" data-id=\"2aeb82a\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Foam bladder tank comparison table<\/h2>\n<p>The data below comes from AZEIDK&#8217;s product pages, which in turn quote the manufacturers&#8217; catalogues and UL records. Where a cell says &#8220;not stated&#8221;, the page simply does not give that item; it does not mean the product lacks it.<\/p>\n<div class=\"az-table-wrap\"><table><thead><tr><th>Item<\/th><th>WATEX<\/th><th>FIRETECH<\/th><th>Falcon Gold<\/th><th>SFFECO<\/th><\/tr><\/thead><tbody>\n<tr><td>Published approval<\/td><td>UL, certificate EX29807 to UL 162<\/td><td>UL, file EX15733<\/td><td>Not stated on the product page<\/td><td>Not stated on the product page<\/td><\/tr>\n<tr><td>Capacity<\/td><td>Vertical 200 to 7,500 L; horizontal 1,000 to 15,000 L<\/td><td>100 to 20,000 L<\/td><td>About 189 to 12,000 L (50 to 3,200 gal)<\/td><td>Per model datasheet<\/td><\/tr>\n<tr><td>Rated pressure<\/td><td>175 psi<\/td><td>12.06 bar (175 psi)<\/td><td>175 psi (about 12 bar)<\/td><td>Per datasheet<\/td><\/tr>\n<tr><td>Test pressure<\/td><td>18.5 kg\/cm\u00b2 (1.5 x rated)<\/td><td>18 bar<\/td><td>1.5 x working pressure<\/td><td>Per datasheet<\/td><\/tr>\n<tr><td>Design code<\/td><td>ASME Section VIII Div. 1<\/td><td>ASME Section VIII Div. 1<\/td><td>ASME Section VIII<\/td><td>Not stated<\/td><\/tr>\n<tr><td>Vessel material<\/td><td>SA-516 Gr. 70<\/td><td>Carbon steel, or stainless 304\/L or 316\/L<\/td><td>Carbon steel<\/td><td>Stainless steel or metal alloy, by application<\/td><\/tr>\n<tr><td>Bladder<\/td><td>Fabric-reinforced nitrile (Buna-N), replaceable on site through the manhole<\/td><td>Nylon-reinforced nitrile, UL listed for AFFF 1%, 3% and AR-AFFF 3&#215;3%<\/td><td>Nylon-reinforced Buna-N<\/td><td>Not stated<\/td><\/tr>\n<tr><td>Orientation<\/td><td>Vertical and horizontal<\/td><td>Vertical and horizontal<\/td><td>Vertical and horizontal<\/td><td>Vertical and horizontal<\/td><\/tr>\n<tr><td>Ratio controller<\/td><td>65 to 200 NB, models WTX-BT and WTX-SS<\/td><td>Ratio-flow controller within the listing<\/td><td>Optional, pre-piped to the tank<\/td><td>Works with a ratio controller<\/td><\/tr>\n<\/tbody><\/table><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-d7c8742 elementor-widget elementor-widget-text-editor\" data-id=\"d7c8742\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>WATEX: UL listed tank and ratio controller<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/watex-ul-foam-bladder-tank\/\">WATEX foam bladder tank<\/a> page cites UL certificate EX29807 in the foam concentrate proportioner category under UL 162, covering the ratio-flow controller with ASME horizontal tanks of 264 to 3,963 gallons and vertical tanks of 53 to 1,982 gallons. Minimum working pressure is 30 psi, operating temperature 2 to 65 \u00b0C, finish fire red RAL 3000, and the manufacturer gives a five-year warranty. Sizing and ratio controller selection are covered in our <a href=\"\/en\/sa\/media-center\/watex-foam-bladder-tanks-ul-saudi\/\">WATEX foam bladder tanks<\/a> guide.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-8aced7e elementor-widget elementor-widget-text-editor\" data-id=\"8aced7e\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>FIRETECH: widest capacity range and a reserve tank option<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/firetech-ul-foam-bladder-tank-vertical-horizontal\/\">FIRETECH foam bladder tank<\/a> page cites UL file EX15733 for the ratio-flow controller with bladder tank, with ASME vertical tanks of 25 to 3,963 gallons and horizontal tanks of 53 to 5,300 gallons in the listing. From the datasheet: 100 to 20,000 litres, a flow range of 75 to 36,000 L\/min, coal tar epoxy lining and a fire red polyurethane finish. Options include the ASME U stamp, CE marking and a twin-vessel main and reserve arrangement with switchover, which some consultants ask for where protection cannot be down during refilling.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-7d7bf0c elementor-widget elementor-widget-text-editor\" data-id=\"7d7bf0c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Falcon Gold: a long options list, built to order<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/falcon-gold-vertical-and-horizontal-foam-bladder-tank\/\">Falcon Gold foam bladder tank<\/a> page describes a carbon steel ASME Section VIII vessel rated at 175 psi, a nylon-reinforced Buna-N bladder, a perforated PVC centre tube, brass trim valves with Teflon seats and about 10% extra volume for thermal expansion of the concentrate. Options include a pre-piped proportioner, sight glass, access ladder, stainless trim, salt-water coating and insulation or heat tracing. The page does not quote a UL listing number, so if the specification calls for a particular approval, ask for the document with the technical offer.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-510f715 elementor-widget elementor-widget-text-editor\" data-id=\"510f715\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>SFFECO: SFD-U models, vertical and horizontal<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/sffeco-foam-bladder-tank\/\">SFFECO foam bladder tank<\/a> page lists five models from SFD-U2-BTRFC to SFD-U8-BTRFC in vertical and horizontal versions with a corrosion-resistant finish, for foam deluge and sprinkler systems, fuel storage areas, aircraft hangars and loading racks. Capacity, working pressure and approvals are not given on the page, so they come from the model datasheet when the offer is prepared. The rest of the range is on the <a href=\"\/en\/brand\/sffeco\/\">SFFECO brand page<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-84bdf0b elementor-widget elementor-widget-text-editor\" data-id=\"84bdf0b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How to choose between the four<\/h2>\n<ol><li><strong>Start with the required approval.<\/strong> If the specification calls for a UL listed tank and ratio controller, the published data points to WATEX and FIRETECH; confirm the listing covers the capacity and controller size you need.<\/li><li><strong>Then capacity and orientation.<\/strong> Capacity follows the hydraulic calculation, concentrate percentage and discharge time; orientation follows the floor area and headroom in the room.<\/li><li><strong>Then the concentrate.<\/strong> Make sure the bladder is approved for the concentrate on the project; FIRETECH&#8217;s bladder, for example, is listed for AFFF 1% and 3% and AR-AFFF 3&#215;3%. Concentrate selection is covered in our guide to <a href=\"\/en\/sa\/media-center\/foam-concentrate-brands-saudi\/\">AFFF foam concentrate brands<\/a>.<\/li><li><strong>Then environment and options.<\/strong> Coastal and marine sites need a suitable coating; critical facilities may need a reserve tank.<\/li><li><strong>Finally supply and support.<\/strong> Lead time and spares such as a replacement bladder vary by brand and size.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-fdecab6 elementor-widget elementor-widget-text-editor\" data-id=\"fdecab6\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Common comparison mistakes<\/h2>\n<ul><li>Comparing nominal capacity only, without checking that the listing or approval covers that exact size.<\/li><li>Pairing a UL listed tank with a ratio controller from another brand that is not part of the same listing.<\/li><li>Topping up with a different concentrate from the one already in the tank; see our article on <a href=\"\/en\/sa\/media-center\/mixing-firefighting-foam-concentrates-compatibility-en\/\">mixing firefighting foam concentrates<\/a>.<\/li><li>Skipping concentrate testing after installation; see <a href=\"\/en\/sa\/media-center\/afff-foam-concentrate-shelf-life-testing\/\">AFFF shelf life and testing<\/a>.<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-c5a2459 elementor-widget elementor-widget-text-editor\" data-id=\"c5a2459\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-faq\"><h2>Frequently asked questions<\/h2>\n<details class=\"az-faq__item\"><summary><h3>Which is the best foam bladder tank in Saudi Arabia?<\/h3><\/summary><p>There is no single best brand. The right tank is the one that matches the approval, capacity and concentrate in your project specification.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Which AZEIDK foam tanks are UL listed?<\/h3><\/summary><p>According to the product pages, WATEX (certificate EX29807) and FIRETECH (file EX15733), both with a ratio controller.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>What is the usual working pressure of a foam bladder tank?<\/h3><\/summary><p>The three tanks with published data (WATEX, FIRETECH and Falcon Gold) are rated at 175 psi, about 12 bar.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Does a bladder tank need a pump or power?<\/h3><\/summary><p>No. Fire water pressure squeezes the bladder and drives the concentrate to the ratio controller.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Can the bladder be replaced?<\/h3><\/summary><p>The WATEX page states the bladder can be replaced on site through the manhole. For the other brands, check the datasheet or ask the AZEIDK team.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>When do I need a main and reserve tank?<\/h3><\/summary><p>When the specification or consultant requires protection to stay available during refilling or maintenance; FIRETECH lists this arrangement as an option.<\/p><\/details>\n<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-11d2e1c elementor-widget elementor-widget-text-editor\" data-id=\"11d2e1c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Summary<\/h2>\n<p>The four foam bladder tanks AZEIDK supplies work on the same principle; they differ in published approval, capacity range and options. Start from the specification, then capacity, concentrate and environment, and ask for approval documents with the technical offer. The AZEIDK team will select the tank and ratio controller from your project data.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-73935ff elementor-widget elementor-widget-text-editor\" data-id=\"73935ff\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-cta\"><strong>Need a foam bladder tank for a project?<\/strong> Send the concentrate type and percentage, solution flow, discharge time and required approval, and the AZEIDK team will recommend the tank and ratio controller. <a href=\"\/en\/sa\/contact\/\">Contact AZEIDK<\/a><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t","protected":false},"excerpt":{"rendered":"<p>Comparing the foam bladder tanks AZEIDK supplies (WATEX, FIRETECH, Falcon Gold, SFFECO) by UL approval, capacity range, working pressure and bladder material.<\/p>\n","protected":false},"author":0,"featured_media":29585,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[221,321,323,322],"tags":[],"azeidk_region":[223],"class_list":["post-29589","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-azeidk-articles","category-codes-certifications-en","category-systems-guides-en","category-systems-guides-ar"],"acf":[],"_links":{"self":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/29589","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/types\/post"}],"replies":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/comments?post=29589"}],"version-history":[{"count":0,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/29589\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media\/29585"}],"wp:attachment":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media?parent=29589"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/categories?post=29589"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/tags?post=29589"},{"taxonomy":"azeidk_region","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/azeidk_region?post=29589"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}