{"id":27579,"date":"2026-11-20T15:21:59","date_gmt":"2026-11-20T12:21:59","guid":{"rendered":"https:\/\/azeidkgroup.com\/sa\/media-center\/"},"modified":"2026-11-21T11:29:53","modified_gmt":"2026-11-21T08:29:53","slug":"residential-building-fire-extinguishers-saudi","status":"publish","type":"post","link":"https:\/\/azeidkgroup.com\/en\/sa\/media-center\/residential-building-fire-extinguishers-saudi\/","title":{"rendered":"Residential Building Fire Extinguishers in Apartment Blocks and Towers: Corridors, Car Parks, Electrical and Generator Rooms"},"content":{"rendered":"\t\t<div data-elementor-type=\"wp-post\" data-elementor-id=\"27579\" class=\"elementor elementor-27579 elementor-27578 elementor-bc-flex-widget\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-b8f6a10 e-con-full az-el-article e-flex e-con e-parent\" data-id=\"b8f6a10\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-32e90df elementor-widget elementor-widget-text-editor\" data-id=\"32e90df\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-intro\"><strong>Residential building fire extinguishers<\/strong> in apartment blocks and towers belong in the common areas that the owner or owners&#8217; association is responsible for: an ABC dry powder or foam unit in each floor corridor near the stairs, units at the entrance and lobby, powder units in the basement and car park plus a wheeled unit where the design requires it, and CO2 units in the electrical, generator and fire pump rooms. They are spaced so that no apartment door is more than 22.9 m from the nearest extinguisher.<\/p>\n<p>To compare extinguisher types and choose the right one for each hazard, see our <a href=\"\/en\/sa\/media-center\/fire-extinguishers-building-safety-guide\/\">fire extinguishers<\/a> selection guide for facilities in Saudi Arabia.<\/p>\n<p>This guide is for building owners, compound managers, owners&#8217; associations and the contractors who hand buildings over. It is not about the kitchen extinguisher inside an apartment. It covers where common-area extinguishers go, the right type for each service room, how to protect units in the basement and on the roof, and what a Civil Defense inspector checks when the building is licensed or renewed.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-aa129b7 elementor-widget elementor-widget-text-editor\" data-id=\"aa129b7\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-keybox\"><h2>Key points<\/h2><ul><li>Each floor corridor: ABC powder or foam near the stairs or lift, and more than one unit in long corridors.<\/li><li>Basement and car park: powder units on columns, and a wheeled unit in large car parks as designed.<\/li><li>Electrical, generator and fire pump rooms: CO2, and an automatic unit for small closed rooms.<\/li><li>Roof and exposed areas: a cabinet or cover against sun and dust.<\/li><li>Binding references: SBC 801, Civil Defense and the approved drawings; NFPA 10 tables are the technical reference.<\/li><\/ul><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-ff76921 elementor-widget elementor-widget-text-editor\" data-id=\"ff76921\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Who is responsible for building extinguishers?<\/h2>\n<p>An extinguisher inside an apartment is usually the occupant&#8217;s matter, but corridor, basement and service room units are part of the shared building equipment that the owner or owners&#8217; association supplies and maintains. In larger compounds the facility manager follows up the monthly checks and the maintenance contract. When the safety licence is renewed the whole building is inspected, so one missing unit in the basement can hold up the licence for everyone.<\/p>\n<p>For all systems in residential projects see our <a href=\"\/en\/sa\/industries\/residential-developments\/\">residential developments<\/a> page, and for what a maintenance contract covers see <a href=\"\/en\/sa\/media-center\/residential-buildings-fire-systems-maintenance-contract\/\">fire systems maintenance contracts for residential buildings<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-73d95a8 elementor-widget elementor-widget-text-editor\" data-id=\"73d95a8\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Residential building fire extinguishers by location<\/h2>\n<table><thead><tr><th>Location<\/th><th>Main hazard<\/th><th>Suitable type<\/th><\/tr><\/thead><tbody><tr><td>Floor corridors<\/td><td>Class A<\/td><td>ABC powder or foam near the stairs or lift<\/td><\/tr><tr><td>Entrance, lobby and guard room<\/td><td>Class A and electrical equipment<\/td><td>ABC powder, small CO2 near control panels<\/td><\/tr><tr><td>Basement and car park<\/td><td>Class A and B (vehicles, fuel)<\/td><td>ABC powder on columns, wheeled unit in large car parks<\/td><\/tr><tr><td>Electrical and meter room<\/td><td>Class C<\/td><td>CO2, and an automatic unit for the closed room<\/td><\/tr><tr><td>Generator room and diesel tank<\/td><td>Class B and C<\/td><td>ABC powder or CO2 as designed<\/td><\/tr><tr><td>Fire pump and water pump room<\/td><td>Class C and motors<\/td><td>CO2 or ABC powder<\/td><\/tr><tr><td>Refuse room<\/td><td>Class A<\/td><td>ABC powder or foam outside the room door<\/td><\/tr><tr><td>Roof and AC plant<\/td><td>Class A and C<\/td><td>ABC powder in a cabinet or under a cover<\/td><\/tr><\/tbody><\/table>\n<p>For fire classes see <a href=\"\/en\/sa\/media-center\/fire-classes-triangle\/\">the fire triangle and fire classes<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-031bc66 elementor-widget elementor-widget-text-editor\" data-id=\"031bc66\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How many extinguishers per floor?<\/h2>\n<p>The designer assigns the hazard class of each zone. If residential floors are classed as light hazard, the NFPA 10 table for Class A sets the smallest single unit at 2-A, each unit of A covers about 279 m\u00b2, and no single unit is credited with more than about 1,045 m\u00b2. In practice the rule that governs on residential floors is travel distance: 22.9 m along the walking path from any point to the nearest unit.<\/p>\n<p>A worked example: on a floor with a 30 m corridor and a central stair, one unit at the stair puts the farthest door about 15 m away, which meets the distance rule. In a tower with a 70 m corridor and stairs at both ends, one unit at each stair leaves the middle of the corridor about 35 m from either, so a third unit is needed in the middle near the lifts. The approved drawings set the final number.<\/p>\n<ul><li><strong>Recessed cabinets in narrow corridors<\/strong> keep the unit out of the way of residents and furniture moves. See <a href=\"\/en\/sa\/media-center\/fire-extinguisher-cabinet-saudi\/\">fire extinguisher cabinets<\/a>.<\/li><li><strong>A fixed wall bracket<\/strong> for exposed units at the correct height. See <a href=\"\/en\/sa\/media-center\/fire-extinguisher-stand-bracket-saudi\/\">fire extinguisher brackets and stands<\/a>.<\/li><li><strong>A sign<\/strong> above every unit, visible from the corridor. See <a href=\"\/en\/sa\/media-center\/fire-extinguisher-sign\/\">the fire extinguisher sign<\/a>.<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-20d77cb elementor-widget elementor-widget-text-editor\" data-id=\"20d77cb\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Basements and car parks<\/h2>\n<p>The basement is where building extinguishers are most often neglected: vehicles, fuel, poor lighting and columns that block the view. Mount units on columns along the driving aisles and at stair entrances, so a driver can reach one a short walk from the car, with a clear sign. In large car parks the designer adds a wheeled powder unit near the ramp or entrance. For wheeled unit sizes see <a href=\"\/en\/sa\/media-center\/wheeled-fire-extinguisher-falcon-gold\/\">wheeled fire extinguishers<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-2a51c6b elementor-widget elementor-widget-text-editor\" data-id=\"2a51c6b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Service rooms and the roof<\/h2>\n<p>The electrical and meter room is usually locked and entered only for maintenance. Place a CO2 unit directly outside its door so the responder picks it up before going in; the designer may also add a ceiling automatic unit that operates on its own if the temperature rises. See <a href=\"\/en\/sa\/media-center\/automatic-ceiling-fire-extinguisher\/\">the automatic ceiling extinguisher<\/a>.<\/p>\n<p>On the roof, with AC units and water tanks, direct sun and dust damage the label and hose and heat the cylinder. Put the unit in a cabinet or under a suitable cover. See <a href=\"\/en\/sa\/media-center\/fire-extinguisher-covers\/\">outdoor fire extinguisher covers<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-5f96ead elementor-widget elementor-widget-text-editor\" data-id=\"5f96ead\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Steps to equip an existing building<\/h2>\n<ol><li>Get the approved drawings; if they are not available, sketch each floor showing the corridor, stairs, lifts and service rooms.<\/li><li>Measure each corridor and set the number of units so no door is more than 22.9 m away.<\/li><li>Add basement units on columns, plus units for the electrical, generator, pump and refuse rooms and the roof.<\/li><li>Choose the type for each location from the table above and check the rating on the datasheet.<\/li><li>Fit brackets or cabinets and signs, and give every unit a number on a single location list.<\/li><li>Sign a maintenance contract covering periodic checks, recharging and testing, and keep the monthly check record ready for inspection.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-23d210f elementor-widget elementor-widget-text-editor\" data-id=\"23d210f\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Common faults in residential buildings<\/h2>\n<ul><li>One unit at the entrance for the whole building, with floors and basement uncovered.<\/li><li>Units stolen or taken into apartments and never replaced.<\/li><li>A basement unit behind a parked car or in a dark corner.<\/li><li>A powder unit inside a locked electrical room reachable only with a key.<\/li><li>Roof units left in the sun until the label fades.<\/li><li>Expired service tags because there is no maintenance contract. See <a href=\"\/en\/sa\/media-center\/fire-extinguisher-maintenance-refill\/\">fire extinguisher maintenance<\/a>.<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6c3ab3f elementor-widget elementor-widget-text-editor\" data-id=\"6c3ab3f\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Building extinguishers available from AZEIDK<\/h2>\n<p>Through its <a href=\"\/en\/sa\/services\/technical-supply-of-fire-safety-systems\/\">technical supply service<\/a>, AZEIDK supplies common-area extinguishers with the datasheet for each model:<\/p>\n<ul><li><a href=\"\/en\/sa\/products\/fg-dry-powder-fire-extinguisher-6kg\/\">FG 6 kg dry powder<\/a>: rated 27A 144BC per the datasheet, for floor corridors and basements.<\/li><li><a href=\"\/en\/sa\/products\/dry-powder-fire-extinguisher-6kg-falcon-gold\/\">Falcon Gold 6 kg dry powder (FDP6)<\/a>: 8 m range and 15 s discharge per the datasheet.<\/li><li><a href=\"\/en\/sa\/products\/fg-wheeled-dry-powder-fire-extinguisher-50kg\/\">FG 50 kg wheeled dry powder<\/a>: for large car parks, rated 55A 233BC.<\/li><li><a href=\"\/en\/sa\/products\/fg-co2-fire-extinguisher-6kg\/\">FG 6 kg CO2<\/a>: for electrical, generator and pump rooms.<\/li><li><a href=\"\/en\/sa\/products\/fg-automatic-fire-extinguisher-hfc-227ea-6kg\/\">FG HT-AT6 automatic extinguisher<\/a>: 6 kg HFC-227ea operating at 68\u00b0C, for small electrical and generator rooms.<\/li><li><a href=\"\/en\/sa\/products\/falcon-gold-recessed-fire-extinguisher-cabinet\/\">Falcon Gold recessed extinguisher cabinet<\/a> (FG-400SG, FG-400M, FG-400S): body about 280 \u00d7 600 \u00d7 180 mm.<\/li><\/ul>\n<p>AZEIDK&#8217;s own team maintains extinguishers under its <a href=\"\/en\/sa\/services\/annual-maintenance-contracts\/\">periodic maintenance contracts<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-c437427 elementor-widget elementor-widget-text-editor\" data-id=\"c437427\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>FAQ<\/h2><div class=\"az-faq\"><details class=\"az-faq__item\"><summary><h3>How many fire extinguishers does an apartment building need?<\/h3><\/summary><p>At least one per floor near the stairs, more where any door is over 22.9 m away, plus units in the basement and service rooms.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>Who pays for corridor extinguishers, owner or tenant?<\/h3><\/summary><p>Common-area units are normally the owner&#8217;s or owners&#8217; association&#8217;s responsibility; anything inside the apartment depends on the lease.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>Which extinguisher suits a basement car park?<\/h3><\/summary><p>Portable ABC powder on columns, plus a wheeled unit in large car parks if the design requires it.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>Where does the electrical room extinguisher go?<\/h3><\/summary><p>Directly outside the door so the responder takes it before entering; an automatic unit may be added inside.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>How do I stop corridor extinguishers being stolen?<\/h3><\/summary><p>A recessed cabinet with an easy-open sealed door and regular monthly checks help spot missing units quickly.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>Do corridor extinguishers replace the fire alarm?<\/h3><\/summary><p>No. Extinguishers are for early response; alarm and other systems follow the approved drawings under SBC 801.<\/p><\/details><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-c1f354c elementor-widget elementor-widget-text-editor\" data-id=\"c1f354c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Summary<\/h2>\n<p>Work through the common areas floor by floor, then the basement, service rooms and roof, match each location to the right type, and tie the units to a maintenance contract with a recorded monthly check. The building passes inspection and residents find an extinguisher when they need one.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-0d97f68 elementor-widget elementor-widget-text-editor\" data-id=\"0d97f68\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-related\">Related reading: <a href=\"\/en\/sa\/media-center\/mall-fire-extinguishers-saudi\/\">Mall Fire Extinguishers<\/a>, <a href=\"\/en\/sa\/media-center\/hotel-fire-extinguishers-saudi\/\">Hotel Fire Extinguishers<\/a> and <a href=\"\/en\/sa\/media-center\/fire-extinguishers-madinah\/\">Fire Extinguishers in Madinah<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6d3e56f elementor-widget elementor-widget-text-editor\" data-id=\"6d3e56f\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-cta\"><strong>Managing a building or compound and need extinguishers fitted or reviewed?<\/strong> Send us the number of floors and the drawings, and we will propose types and quantities with a supply and maintenance offer. <a href=\"\/en\/sa\/contact\/\">Contact the AZEIDK team<\/a><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-25af4ec elementor-widget elementor-widget-text-editor\" data-id=\"25af4ec\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-source\"><strong>References:<\/strong> <a href=\"https:\/\/regulations.justia.com\/states\/massachusetts\/780-cmr\/chapter-9\/section-906\/subsection-906-3\" rel=\"noopener\" target=\"_blank\">Section 906.3, Tables 906.3(1) and 906.3(2)<\/a> (780 CMR, NFPA 10 tables); <a href=\"https:\/\/ehs.ucf.edu\/wp-content\/uploads\/sites\/3\/2025\/08\/SB041-Fire-Extinguisher-Fact-Sheet-II.pdf\" rel=\"noopener\" target=\"_blank\">Fire Extinguisher Location and Placement<\/a> (NFPA, November 2022); AZEIDK product pages and datasheets.<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t","protected":false},"excerpt":{"rendered":"<p>Residential building fire extinguishers for common areas: a powder unit per floor, basement and car park units, CO2 for electrical rooms, within 22.9 m.<\/p>\n","protected":false},"author":0,"featured_media":27718,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[221,323,327,322],"tags":[],"azeidk_region":[223],"class_list":["post-27579","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-azeidk-articles","category-systems-guides-en","category-by-facility-en","category-systems-guides-ar"],"acf":[],"_links":{"self":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/27579","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/types\/post"}],"replies":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/comments?post=27579"}],"version-history":[{"count":2,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/27579\/revisions"}],"predecessor-version":[{"id":28248,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/27579\/revisions\/28248"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media\/27718"}],"wp:attachment":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media?parent=27579"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/categories?post=27579"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/tags?post=27579"},{"taxonomy":"azeidk_region","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/azeidk_region?post=27579"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}