{"id":27084,"date":"2026-11-20T13:33:44","date_gmt":"2026-11-20T10:33:44","guid":{"rendered":"https:\/\/azeidkgroup.com\/sa\/media-center\/"},"modified":"2026-11-20T13:35:08","modified_gmt":"2026-11-20T10:35:08","slug":"lift-shaft-pressurization-saudi","status":"publish","type":"post","link":"https:\/\/azeidkgroup.com\/en\/sa\/media-center\/lift-shaft-pressurization-saudi\/","title":{"rendered":"Lift Shaft Pressurization: Required Pressure Difference, a Fan per Shaft, Door Testing and Fire Alarm Interface"},"content":{"rendered":"\t\t<div data-elementor-type=\"wp-post\" data-elementor-id=\"27084\" class=\"elementor elementor-27084 elementor-27083 elementor-bc-flex-widget\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-4edac0c e-con-full az-el-article e-flex e-con e-parent\" data-id=\"4edac0c\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-e8cc004 elementor-widget elementor-widget-text-editor\" data-id=\"e8cc004\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-intro\"><strong>Lift shaft pressurization<\/strong> (elevator hoistway pressurization) pushes clean air into the lift shaft during a fire, so the shaft is at a slightly higher pressure than the floors around it. Smoke then cannot enter the shaft through the landing doors and travel between floors. It is typically required in high-rise buildings and for firefighter and evacuation lifts, depending on project requirements.<\/p>\n<p>This guide covers how the system works, the pressure limits as stated in the US IBC, its components, how it ties into the fire alarm and how it is tested before handover. AZEIDK delivers these systems under its <a href=\"\/en\/sa\/solutions\/smoke-extraction-emergency-ventilation-systems\/\">smoke extraction and emergency ventilation systems<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-2cdd8c9 elementor-widget elementor-widget-text-editor\" data-id=\"2cdd8c9\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-keybox\"><h2>Key takeaways<\/h2><ul><li>A lift shaft is an open vertical path between floors; smoke that gets in spreads quickly.<\/li><li>IBC Section 909.21 (as quoted by ICC from the 2012 edition) sets a pressure difference of at least 0.10 in. of water (25 Pa) and no more than 0.25 in. of water (67 Pa).<\/li><li>The upper limit matters as much as the lower one, because excess pressure can stop the lift doors from working.<\/li><li>Each shaft has its own fan system, and a smoke detector stops the fan if it draws in smoke.<\/li><li>Shaft fans are controlled from the firefighter&#8217;s smoke control panel.<\/li><\/ul><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-22f92b6 elementor-widget elementor-widget-text-editor\" data-id=\"22f92b6\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Why does a lift shaft need positive pressure?<\/h2>\n<p>In multi-storey buildings a lift shaft acts like a chimney. Stack effect, HVAC air movement and open doors all push smoke towards vertical openings. Smoke that enters the shaft on the fire floor can come out on floors far from the fire.<\/p>\n<p>Pressurization reverses the leakage: air flows out of the shaft into the floors through door gaps instead of smoke flowing in. The principle is the same as <a href=\"\/en\/sa\/media-center\/smoke-control-stair-pressurization\/\">stair pressurization for escape routes<\/a>, but shafts have their own issues: power-operated doors, lift recall during a fire, and sometimes a connected machine room.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6c42d17 elementor-widget elementor-widget-text-editor\" data-id=\"6c42d17\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Required pressure difference for lift shaft pressurization<\/h2>\n<p>In Saudi Arabia the Saudi Building Code, Civil Defense requirements and the approved project design govern. The values below are from US IBC Section 909.21, a common technical reference for these systems; the designer confirms the corresponding clause in the edition adopted in the Kingdom.<\/p>\n<div class=\"az-table-wrap\"><table><thead><tr><th>Item<\/th><th>Value as quoted by ICC from IBC 2012 Section 909.21<\/th><\/tr><\/thead><tbody><tr><td>Minimum pressure difference<\/td><td>0.10 in. of water (25 Pa) positive relative to adjacent occupied space on all floors<\/td><\/tr><tr><td>Maximum pressure difference<\/td><td>0.25 in. of water (67 Pa)<\/td><\/tr><tr><td>Measurement point<\/td><td>Midpoint of each hoistway door<\/td><\/tr><tr><td>Door condition during measurement<\/td><td>All hoistway doors on the recall floor open, all other hoistway doors closed<\/td><\/tr><tr><td>Door operation<\/td><td>Doors shown to open and close at each level with the system running<\/td><\/tr><\/tbody><\/table><\/div>\n<p>Why a maximum? Lift doors are driven by small operators, and excess pressure can stop them closing or slow them down, taking the lift out of service just when firefighters need it. The system is therefore designed to stay inside a band however many doors are open.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-8d6b8aa elementor-widget elementor-widget-text-editor\" data-id=\"8d6b8aa\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Components of a lift shaft pressurization system<\/h2>\n<ul><li><strong>Dedicated supply fan per shaft:<\/strong> the same ICC document quotes a separate fan system for each hoistway.<\/li><li><strong>Outdoor air intake:<\/strong> placed away from exhaust and smoke outlets so the fan does not draw smoke into the shaft.<\/li><li><strong>Smoke detector at the intake or in the supply path:<\/strong> shuts the fan down if smoke is detected in incoming air.<\/li><li><strong>Ducts and fans with the shaft&#8217;s fire-resistance rating:<\/strong> as quoted from the IBC.<\/li><li><strong>Pressure regulation:<\/strong> for example fan speed control with a VFD driven by a pressure sensor, keeping pressure inside the band as doors open and close.<\/li><li><strong>Standby power and fire-resistant cabling:<\/strong> the system must keep running during a fire.<\/li><\/ul>\n<h3>Is shaft venting still needed?<\/h3>\n<p>Some codes required a vent at the top of the lift shaft to release smoke. In Washington State&#8217;s amendments to Section 909, for example, hoistway venting is not needed for pressurized shafts, and machine rooms are pressurized unless separated from the shaft by fire-rated construction. Each project settles this under the adopted code and the authority&#8217;s requirements.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-01e5506 elementor-widget elementor-widget-text-editor\" data-id=\"01e5506\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Connecting lift shaft pressurization to the fire alarm<\/h2>\n<p>The system usually starts on a signal from the fire alarm panel through an output module, written in the <a href=\"\/en\/sa\/media-center\/fire-alarm-cause-and-effect-matrix\/\">cause and effect matrix<\/a> alongside lift recall, stair pressurization and AHU shutdown. Points to agree early between the fire engineer, mechanical engineer and lift supplier:<\/p>\n<ul><li>Which signals start the system: any detector in the building or specific zones.<\/li><li>Order of commands between lift recall and fan start, so door movement is not affected during recall.<\/li><li>Fault signals from the fan and intake detector, and how they show on the fire alarm panel.<\/li><li>Manual control: IBC 909.16 (as adopted in the Massachusetts code) requires the firefighter&#8217;s smoke control panel to give ON-AUTO-OFF control over each piece of smoke control equipment, including elevator shaft fans.<\/li><\/ul>\n<p>For interfacing signals on addressable systems, see <a href=\"\/en\/sa\/media-center\/addressable-input-output-module-fire-alarm-interface\/\">fire alarm input\/output modules<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-90a1d46 elementor-widget elementor-widget-text-editor\" data-id=\"90a1d46\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How is lift shaft pressurization tested before handover?<\/h2>\n<ol><li>Check the shaft is complete: doors installed and adjusted, gaps around doors and cables sealed as drawn.<\/li><li>Start the system from a real alarm signal and check fan start and response time.<\/li><li>Measure the pressure difference at the midpoint of each door on every floor, with doors set as the code and design require.<\/li><li>Open and close the doors on each floor with the system running.<\/li><li>Simulate smoke at the intake or trigger its detector, and confirm the fan stops and the signal appears.<\/li><li>Test manual control from the firefighter&#8217;s panel.<\/li><\/ol>\n<p>This test belongs to <a href=\"\/en\/sa\/media-center\/integrated-fire-life-safety-systems-testing\/\">integrated fire and life safety systems testing<\/a>, as it brings together the alarm, lifts and ventilation. Pressure measurement details are in <a href=\"\/en\/sa\/media-center\/smoke-control-system-testing-commissioning\/\">smoke control system testing<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-a3e4b18 elementor-widget elementor-widget-text-editor\" data-id=\"a3e4b18\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Common mistakes<\/h2>\n<ul><li>Air intake near a smoke exhaust or generator exhaust outlet, so the system pulls smoke into the shaft.<\/li><li>Fixed-speed fan with no regulation, so pressure exceeds the maximum when doors close.<\/li><li>Unsealed openings in shaft walls or around landing doors, so the minimum is never reached however big the fan.<\/li><li>No coordination with the lift supplier on door closing force and recall sequence.<\/li><li>Ordinary cabling or a non-standby power source for the fan.<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-e19496f elementor-widget elementor-widget-text-editor\" data-id=\"e19496f\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Lift shaft pressurization with AZEIDK<\/h2>\n<p>Under its <a href=\"\/en\/sa\/solutions\/smoke-extraction-emergency-ventilation-systems\/\">smoke extraction and emergency ventilation systems<\/a>, AZEIDK handles site study, supply and installation of fans and control components, connection to the fire alarm and testing. Fan capacities and positions follow the approved design for each project, and our <a href=\"\/en\/sa\/services\/engineering-design-calculations\/\">engineering design and calculations<\/a> service can review the design and coordination with HVAC and lifts.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-b39d738 elementor-widget elementor-widget-text-editor\" data-id=\"b39d738\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Frequently asked questions<\/h2>\n<div class=\"az-faq\"><details class=\"az-faq__item\"><summary><h3>What is lift shaft pressurization?<\/h3><\/summary><p>A system that supplies clean air into the lift shaft during a fire so it stays at higher pressure than the floors, keeping smoke out of the shaft.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>What pressure difference is required?<\/h3><\/summary><p>ICC quotes IBC 2012 at a minimum of 0.10 in. of water (25 Pa) and a maximum of 0.25 in. of water (67 Pa); each project follows its adopted code and authority.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>How is it different from stair pressurization?<\/h3><\/summary><p>Same principle, but lift shafts must allow for power-operated doors and lift recall, so the upper pressure limit is tighter.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>Does each lift shaft need its own fan?<\/h3><\/summary><p>According to the IBC text quoted by ICC, yes: a separate fan system for each hoistway.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>When does the system start?<\/h3><\/summary><p>On a fire signal from the alarm panel under the cause and effect matrix, with manual control from the firefighter smoke control panel.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>What if smoke enters the air intake?<\/h3><\/summary><p>The intake smoke detector stops the fan so it does not push smoke into the shaft, and the signal shows on the fire alarm panel.<\/p><\/details><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-af75159 elementor-widget elementor-widget-text-editor\" data-id=\"af75159\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Conclusion<\/h2>\n<p>Lift shaft pressurization works between two limits: enough pressure to keep smoke out, and not so much that lift doors fail. That takes a dedicated fan per shaft, a clean air intake, pressure regulation, a planned interface with the alarm and lifts, and a floor-by-floor test before handover.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-427465b elementor-widget elementor-widget-text-editor\" data-id=\"427465b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-cta\"><strong>Does your project include firefighter lifts or shafts that need pressurization?<\/strong> Send us the drawings and Civil Defense requirements, and we will review supply, installation, interfacing and testing with you. <a href=\"\/en\/sa\/contact\/\">Talk to the AZEIDK team<\/a><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-867bf8e elementor-widget elementor-widget-text-editor\" data-id=\"867bf8e\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-source\"><strong>References:<\/strong> <a href=\"https:\/\/iccsafe.org\/wp-content\/uploads\/ctc\/ElevatorLobby.pdf\" rel=\"noopener\" target=\"_blank\">ICC Code Technology Committee, Elevator Lobby proposals F194-13 (quotes 2012 IBC Section 909.21)<\/a>, <a href=\"https:\/\/lawfilesext.leg.wa.gov\/Law\/WACArchive\/2020\/htm\/WAC%20%2051%20%20TITLE\/WAC%20%2051%20-%2054A%20CHAPTER\/WAC%20%2051%20-%2054A-0909.htm\" rel=\"noopener\" target=\"_blank\">WAC 51-54A-0909 Smoke control systems (Washington State amendments to IFC Section 909)<\/a>, <a href=\"https:\/\/regulations.justia.com\/states\/massachusetts\/780-cmr\/chapter-9\/section-909\/subsection-909-16\" rel=\"noopener\" target=\"_blank\">780 CMR 909.16 Fire-fighter&#8217;s smoke control panel (Massachusetts building code text)<\/a><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t","protected":false},"excerpt":{"rendered":"<p>Lift shaft pressurization: how it keeps smoke out, the 25 to 67 Pa limits quoted from the IBC, a fan per shaft, air intake, fire alarm interface and testing.<\/p>\n","protected":false},"author":0,"featured_media":27038,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[221,323,329,322],"tags":[],"azeidk_region":[223],"class_list":["post-27084","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-azeidk-articles","category-systems-guides-en","category-operation-maintenance-en","category-systems-guides-ar"],"acf":[],"_links":{"self":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/27084","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/types\/post"}],"replies":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/comments?post=27084"}],"version-history":[{"count":1,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/27084\/revisions"}],"predecessor-version":[{"id":27192,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/27084\/revisions\/27192"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media\/27038"}],"wp:attachment":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media?parent=27084"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/categories?post=27084"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/tags?post=27084"},{"taxonomy":"azeidk_region","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/azeidk_region?post=27084"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}