{"id":25193,"date":"2026-11-14T16:09:32","date_gmt":"2026-11-14T13:09:32","guid":{"rendered":"https:\/\/azeidkgroup.com\/sa\/media-center\/"},"modified":"2026-11-14T17:10:33","modified_gmt":"2026-11-14T14:10:33","slug":"smoke-detector-sensitivity-testing-cleaning","status":"publish","type":"post","link":"https:\/\/azeidkgroup.com\/en\/sa\/media-center\/smoke-detector-sensitivity-testing-cleaning\/","title":{"rendered":"Smoke Detector Sensitivity Testing and Cleaning on Addressable Systems (NFPA 72)"},"content":{"rendered":"\t\t<div data-elementor-type=\"wp-post\" data-elementor-id=\"25193\" class=\"elementor elementor-25193 elementor-25192 elementor-bc-flex-widget\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-b6ac634 e-con-full az-el-article e-flex e-con e-parent\" data-id=\"b6ac634\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-236bb1b elementor-widget elementor-widget-text-editor\" data-id=\"236bb1b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-intro\">Smoke detector sensitivity testing measures whether a smoke detector is still within its listed and marked sensitivity range: not so dull that it alarms late, and not so sensitive that it causes false alarms. Under NFPA 72 it is not required at installation. It is done within one year of installation, then every other year, and the interval can be extended after that under conditions. A detector found outside its range is cleaned and recalibrated, or replaced.<\/p>\n<p>This article is for facility managers and maintenance engineers in Saudi Arabia who see a &#8220;dirty detector&#8221; or maintenance message on an addressable panel and want to know what is actually required: whether cleaning is enough, when measurement is due, and when replacement is the right call. It is part of our <a href=\"\/en\/sa\/services\/annual-maintenance-contracts\/\">preventive and periodic maintenance<\/a> service for <a href=\"\/en\/sa\/solutions\/fire-alarm-systems\/\">fire alarm systems<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-1ff4f20 elementor-widget elementor-widget-text-editor\" data-id=\"1ff4f20\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-keybox\"><h2>Key takeaways<\/h2><ul>\n<li>The annual functional test shows a detector responds. The sensitivity test shows its response is still within the listed range. One does not replace the other.<\/li>\n<li>The NFPA 72 schedule: within one year of installation, then every other year, with extension to five years after the second test if the detector stays within range.<\/li>\n<li>Measurement uses a calibrated method: a manufacturer&#8217;s instrument, a listed panel that reads sensitivity, or another calibrated method accepted by the authority.<\/li>\n<li>A dirty detector message on an addressable panel is an early warning that dust is approaching the limit. Its exact wording and meaning come from the panel manual.<\/li>\n<li>A detector outside its range is cleaned and measured again. If it does not come back within range, it is replaced.<\/li>\n<\/ul><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-632eacb elementor-widget elementor-widget-text-editor\" data-id=\"632eacb\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>What is smoke detector sensitivity testing, and how is it different from a functional test?<\/h2>\n<p>Every listed smoke detector has a sensitivity range set by the manufacturer and marked on the detector or stated in its datasheet. Over time, dust and insect debris build up in the sensing chamber and shift the detector&#8217;s baseline. It may become more sensitive and alarm with no fire, or less sensitive and wait until smoke reaches a higher concentration.<\/p>\n<p>The annual functional test introduces smoke or an approved simulant and confirms the signal reaches the panel. It answers one question: does the detector work? It does not measure the concentration at which it works. That is why NFPA 72 separates the two tests and gives sensitivity testing its own schedule in 14.4.4.3 of Chapter 14.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-321dd0d elementor-widget elementor-widget-text-editor\" data-id=\"321dd0d\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>When is smoke detector sensitivity testing required under NFPA 72?<\/h2>\n<p>According to Electrical Contractor&#8217;s explanation of 14.4.4.3 (March 2022), the schedule runs like this:<\/p>\n<ul>\n<li>Sensitivity testing is not required when detectors are first installed, because the acceptance test covers that stage.<\/li>\n<li>The first measurement is made within one year of installation.<\/li>\n<li>It is then repeated every other year.<\/li>\n<li>After the second test, the interval may be extended to five years if the detector stays within range, provided unwanted alarms are tracked and recorded.<\/li>\n<\/ul>\n<p>In Saudi Arabia, the Saudi Fire Protection Code SBC 801 and the requirements of the General Directorate of Civil Defense are the binding framework, and NFPA 72 is used as the technical reference that designers write into specifications and maintenance contracts. Write the sensitivity testing schedule into the contract scope explicitly rather than leaving it implied under &#8220;detector testing&#8221;.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-5eada12 elementor-widget elementor-widget-text-editor\" data-id=\"5eada12\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How is sensitivity measured? Accepted methods<\/h2>\n<p>Spraying a can of test smoke and waiting for the alarm is a functional test, not a sensitivity measurement. Shane Clary, writing in Security Sales &amp; Integration (January 2022), summarises the five accepted sensitivity test methods in NFPA 72 Table 14.4.3.2, all of them calibrated:<\/p>\n<div class=\"az-table-wrap\"><table>\n<thead><tr><th>Method<\/th><th>How it works<\/th><th>Practical note<\/th><\/tr><\/thead>\n<tbody>\n<tr><td>Recognised calibrated test method<\/td><td>Exposes the detector to smoke or listed aerosol at a known concentration<\/td><td>Needs calibration equipment and a result recorded per detector<\/td><\/tr>\n<tr><td>Manufacturer&#8217;s calibrated sensitivity test instrument<\/td><td>A tool from the manufacturer that reads its own detectors<\/td><td>Model-specific, follow the manufacturer&#8217;s manual<\/td><\/tr>\n<tr><td>Listed control equipment arranged for the purpose<\/td><td>The addressable panel reads each detector and reports sensitivity<\/td><td>Common on modern addressable systems<\/td><\/tr>\n<tr><td>Listed detector and control unit arrangement<\/td><td>The detector signals the panel when its sensitivity is outside the listed range<\/td><td>That signal is itself a test result, do not ignore it<\/td><\/tr>\n<tr><td>Other calibrated method<\/td><td>Any calibrated method approved by the code official<\/td><td>Get the approval in writing<\/td><\/tr>\n<\/tbody><\/table><\/div>\n<p>On an addressable system, the simplest route is usually the panel&#8217;s sensitivity report: a list of every detector on the loop with its current reading. Print or export it and attach it to the visit report. It is the strongest evidence that the test was done. For how loops and device addressing work, see <a href=\"\/en\/sa\/media-center\/addressable-fire-alarm-loop-design\/\">addressable fire alarm loop design<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-d3492ba elementor-widget elementor-widget-text-editor\" data-id=\"d3492ba\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>The dirty detector message on an addressable panel: what does it mean?<\/h2>\n<p>Many addressable panels track each smoke detector&#8217;s reading and compensate for the slow drift caused by dust (drift compensation), raising a warning before it turns into a false alarm or a fault. One documented example: the datasheet for the <a href=\"\/en\/sa\/products\/notifier-nfs2-640-addressable-fire-alarm-panel\/\">Notifier NFS2-640<\/a> panel (DN-7111:L) states that drift compensation lets the detector keep its original ability to detect smoke, and that the panel performs the periodic sensitivity measurements automatically in line with NFPA 72. It describes warning levels including &#8220;Maintenance Alert&#8221;, when dust accumulation is near but below the allowed limit, and &#8220;Maintenance Urgent&#8221;, when it is above the allowed limit. Other panels use the word &#8220;Dirty&#8221; or different wording.<\/p>\n<p>Three points matter here:<\/p>\n<ol>\n<li><strong>Go to the panel manual.<\/strong> The wording, the levels and what to do at each level are set by the operating manual for that panel model, not by a general interpretation.<\/li>\n<li><strong>Do not ignore the warning because no alarm has happened yet.<\/strong> The early warning is your chance to clean the detector on a planned visit instead of answering a false alarm at night.<\/li>\n<li><strong>Do not delete or disable the detector to silence the message.<\/strong> A disabled detector means an unprotected area, and it must be recorded and dealt with quickly.<\/li>\n<\/ol>\n<p>If the message keeps appearing for detectors in one area, the problem is usually the environment rather than the detector: fit-out dust, an air-conditioning outlet nearby, or a nearby kitchen. We covered these causes in <a href=\"\/en\/sa\/media-center\/fire-alarm-false-alarms-causes\/\">fire alarm false alarms: causes<\/a>, and other panel faults in <a href=\"\/en\/sa\/media-center\/fire-alarm-panel-faults-troubleshooting\/\">fire alarm panel faults and repair<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-ff35ca2 elementor-widget elementor-widget-text-editor\" data-id=\"ff35ca2\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Cleaning smoke detectors: what to do and what to avoid<\/h2>\n<p>Detectors are cleaned in line with the manufacturer&#8217;s published documentation, as Electrical Contractor points out. Methods vary between models, because some allow the chamber cover to be opened and some do not. The steps below are general practice, adapted to the manual:<\/p>\n<ul>\n<li>Notify building management and the monitoring party before starting, and put the panel or zone into test mode under site procedures.<\/li>\n<li>Remove the detector from its base and clean it only as the manufacturer allows, for example by vacuum or clean compressed air from a suitable distance.<\/li>\n<li>Do not use solvents or cleaning products the manual does not name, and never paint or cover the detector.<\/li>\n<li>Refit the detector and confirm the panel recognises it at the correct address and type.<\/li>\n<li>Read the sensitivity again after cleaning and record the values before and after.<\/li>\n<li>Return the system to normal and inform everyone who was notified.<\/li>\n<\/ul>\n<p>During refurbishment inside an occupied building, dust is the main cause of contaminated detectors. Agree a written procedure with the contractor to cover detectors only in the work area, remove the covers and check the detectors when the work ends, and arrange alternative protection for as long as the covers are on.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-52ad83a elementor-widget elementor-widget-text-editor\" data-id=\"52ad83a\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>When should a smoke detector be replaced instead of cleaned?<\/h2>\n<p>As Shane Clary explains in Security Sales &amp; Integration (January 2022), referring to the test table in Chapter 14 of NFPA 72, a detector found outside its listed sensitivity range must be either cleaned and recalibrated or replaced. In practice the decision can be laid out like this:<\/p>\n<div class=\"az-table-wrap\"><table>\n<thead><tr><th>Condition<\/th><th>Suggested action<\/th><\/tr><\/thead>\n<tbody>\n<tr><td>First dirty detector warning, reading within range<\/td><td>Clean on the next visit and measure again<\/td><\/tr>\n<tr><td>Reading out of range, back within range after cleaning<\/td><td>Keep the detector and follow it on later visits<\/td><\/tr>\n<tr><td>Reading still out of range after cleaning<\/td><td>Replace with a model compatible with the panel<\/td><\/tr>\n<tr><td>Warning returns soon after cleaning<\/td><td>Review the environment and detector type, then replace if it persists<\/td><\/tr>\n<tr><td>Physical damage, paint, heat or moisture inside the detector<\/td><td>Replace<\/td><\/tr>\n<tr><td>Detector past the service life the manufacturer recommends<\/td><td>Replace as the manufacturer recommends<\/td><\/tr>\n<\/tbody><\/table><\/div>\n<p>A replacement detector must be listed for use with the existing panel, given the correct address and functionally tested after installation. Do not confuse a system detector with a standalone battery smoke alarm: they follow different rules. If a smoke detector sits in an environment that does not suit smoke detection at all, such as some kitchens or steamy areas, the answer may be a different detector type after a design review, and <a href=\"\/en\/sa\/media-center\/heat-detector-types-installation\/\">heat detector types and installation<\/a> will help there.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-747ba8e elementor-widget elementor-widget-text-editor\" data-id=\"747ba8e\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How to build sensitivity testing and cleaning into a maintenance contract in Saudi Arabia<\/h2>\n<p>Sensitivity testing tends to get lost between contract items. To avoid that:<\/p>\n<ul>\n<li>List sensitivity testing and its schedule in the contract scope, separate from the annual functional test.<\/li>\n<li>Ask for a sensitivity report per detector, with address, location and reading, not a line saying &#8220;checked&#8221;.<\/li>\n<li>Record every dirty detector warning, its date and the action taken in the fire safety log. That record is what justifies extending the interval later.<\/li>\n<li>State in the contract who supplies replacement detectors and how a compatible model is approved.<\/li>\n<\/ul>\n<p>For the records inspectors usually ask for, see <a href=\"\/en\/sa\/media-center\/fire-safety-log-book-records-inspection\/\">fire safety log book and inspection records<\/a>.<\/p>\n<p>AZEIDK supplies addressable smoke detectors in Saudi Arabia, including the <a href=\"\/en\/sa\/products\/context-ul-plus-optical-smoke-detector-58000-650imc\/\">UL Plus optical smoke detector 58000-650IMC<\/a> and the <a href=\"\/en\/sa\/products\/notifier-fsp-951-addressable-photoelectric-smoke-detector\/\">Notifier FSP-951 addressable photoelectric smoke detector<\/a>, within the <a href=\"\/en\/sa\/products\/?product_category=addressable-fire-alarm-systems\">addressable fire alarm systems<\/a> category. AZEIDK carries out periodic maintenance of fire alarm systems following the manufacturer&#8217;s manual for each panel and detector.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-e68e216 elementor-widget elementor-widget-text-editor\" data-id=\"e68e216\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Frequently asked questions<\/h2>\n<div class=\"az-faq\">\n<details class=\"az-faq__item\"><summary><h3>How often should smoke detector sensitivity be tested?<\/h3><\/summary><p>Under NFPA 72: within one year of installation, then every other year. After the second test the interval may be extended to five years if the detector stays within range and unwanted alarms are tracked.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Is a test with canned smoke enough for a sensitivity test?<\/h3><\/summary><p>No. Canned smoke shows the detector responds, but it does not measure the concentration at which it responds. Sensitivity is measured with one of the five calibrated methods.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>What does a dirty detector message on a fire alarm panel mean?<\/h3><\/summary><p>It usually means the detector is approaching its dust compensation limit and needs cleaning. The wording and levels vary by manufacturer, and the panel manual is the reference.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Can I clean a smoke detector myself?<\/h3><\/summary><p>Cleaning is maintenance work on a live protection system. It needs an orderly isolation of the area and a new measurement afterwards, so it is best done by a maintenance technician following the manufacturer&#8217;s manual and recorded.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>When is replacing a smoke detector better than cleaning it?<\/h3><\/summary><p>When the reading stays out of range after cleaning, the warning returns quickly, the detector is damaged, or it is past the service life the manufacturer recommends.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Do conventional smoke detectors need sensitivity testing too?<\/h3><\/summary><p>Yes, the NFPA 72 schedule applies to smoke detectors generally. The difference is that a conventional panel cannot read sensitivity, so a manufacturer&#8217;s instrument or another calibrated method is used.<\/p><\/details>\n<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-57606f2 elementor-widget elementor-widget-text-editor\" data-id=\"57606f2\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Summary<\/h2>\n<p>Smoke detector sensitivity testing is a programme in its own right: the first measurement within a year, then every other year, using a calibrated method rather than a can of smoke. A dirty detector message on an addressable panel is an early warning, dealt with by cleaning and measuring again, and a detector that does not return to its range is replaced with a compatible model. At inspection, what proves all of this is the sensitivity report and the log.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-3d51b98 elementor-widget elementor-widget-text-editor\" data-id=\"3d51b98\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-cta\"><strong>Seeing dirty detector messages or repeated false alarms?<\/strong> Send us the panel type, the number of loops and the date of the last maintenance visit, and we will propose the inspection and sensitivity measurement scope that fits your system. <a href=\"\/en\/sa\/contact\/\">Talk to the AZEIDK team<\/a><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-d1fbd0b elementor-widget elementor-widget-text-editor\" data-id=\"d1fbd0b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-source\"><strong>References:<\/strong> <a href=\"https:\/\/www.ecmag.com\/magazine\/articles\/article-detail\/integrated-systems-tried-and-tested-smoke-detector-sensitivity-testing\" rel=\"nofollow noopener\" target=\"_blank\">Tried and Tested: Smoke Detector Sensitivity Testing, Electrical Contractor, March 2022<\/a>; <a href=\"https:\/\/www.securitysales.com\/fire-intrusion\/5-approved-methods-testing-smoke-detectors\/\" rel=\"nofollow noopener\" target=\"_blank\">5 Approved Methods for Testing Smoke Detectors, Shane Clary, Security Sales &amp; Integration, January 2022<\/a>; <a href=\"https:\/\/www.honeywellbuildings.in\/assets\/datasheet\/fire\/notifier\/NFS2_640E.pdf\" rel=\"nofollow noopener\" target=\"_blank\">Notifier NFS2-640 Data Sheet DN-7111:L, Honeywell Notifier, 2016<\/a>; <a href=\"https:\/\/www.nfpa.org\/product\/nfpa-72-code\/p0072code\/nfpa-72-national-fire-alarm-and-signaling-code-2025\/7225\" rel=\"nofollow noopener\" target=\"_blank\">NFPA 72, National Fire Alarm and Signaling Code, NFPA<\/a>.<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t","protected":false},"excerpt":{"rendered":"<p>Smoke detector sensitivity test under NFPA 72: when it is due, the accepted calibrated methods, what a dirty detector message means, when to clean or replace.<\/p>\n","protected":false},"author":0,"featured_media":24947,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[221,321,329,320],"tags":[],"azeidk_region":[223],"class_list":["post-25193","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-azeidk-articles","category-codes-certifications-en","category-operation-maintenance-en","category-codes-certifications-ar"],"acf":[],"_links":{"self":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/25193","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/types\/post"}],"replies":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/comments?post=25193"}],"version-history":[{"count":4,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/25193\/revisions"}],"predecessor-version":[{"id":26218,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/25193\/revisions\/26218"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media\/24947"}],"wp:attachment":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media?parent=25193"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/categories?post=25193"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/tags?post=25193"},{"taxonomy":"azeidk_region","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/azeidk_region?post=25193"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}