{"id":25111,"date":"2026-11-14T13:15:00","date_gmt":"2026-11-14T10:15:00","guid":{"rendered":"https:\/\/azeidkgroup.com\/sa\/media-center\/"},"modified":"2026-11-14T13:15:06","modified_gmt":"2026-11-14T10:15:06","slug":"false-waterflow-alarm-sprinkler-retard","status":"publish","type":"post","link":"https:\/\/azeidkgroup.com\/en\/sa\/media-center\/false-waterflow-alarm-sprinkler-retard\/","title":{"rendered":"False Waterflow Alarm Sprinkler Fixes: Alarm Valve Retard and Potter VSR Timer"},"content":{"rendered":"\t\t<div data-elementor-type=\"wp-post\" data-elementor-id=\"25111\" class=\"elementor elementor-25111 elementor-25110 elementor-bc-flex-widget\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-216e391 e-con-full az-el-article e-flex e-con e-parent\" data-id=\"216e391\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-cce8b44 elementor-widget elementor-widget-text-editor\" data-id=\"cce8b44\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-intro\">A false waterflow alarm sprinkler problem means the fire alarm panel received a waterflow signal from the sprinkler system although no sprinkler opened. Most cases come down to three causes: pressure surges from the fire pump or the water supply, air trapped in the piping, and a retard timer set too short or a clogged retard chamber. This article shows how to find which device sent the signal, the alarm check valve or the flow switch, and how to clear the cause step by step. It is part of <a href=\"\/en\/sa\/solutions\/fire-fighting-systems\/\">AZEIDK fire fighting systems<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-bc17622 elementor-widget elementor-widget-text-editor\" data-id=\"bc17622\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-keybox\"><h2>Key takeaways<\/h2><ul>\n<li>On a wet system two devices send the waterflow signal: the pressure switch on the alarm line of the wet alarm check valve, and the vane-type flow switch on the riser or floor branch.<\/li>\n<li>The retard chamber on the AFC ACV-300 delays the alarm by 5 to 60 seconds according to the operation manual. A clogged bottom orifice shortens that delay.<\/li>\n<li>The Potter VSR flow switch has a retard adjustable from 0 to its maximum setting (60 to 90 seconds). The manufacturer says to set it at the minimum needed to prevent false alarms.<\/li>\n<li>Trapped air and leaks on the system side are common causes of intermittent alarms.<\/li>\n<li>Never silence the problem by blocking the vane or closing the alarm line. Bypass the zone at the panel and fix the cause.<\/li>\n<\/ul><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-d6263f6 elementor-widget elementor-widget-text-editor\" data-id=\"d6263f6\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>What is a false waterflow alarm on a sprinkler system?<\/h2>\n<p>In a wet pipe system the piping stays full of water under pressure. When a sprinkler opens, pressure drops on the system side, the alarm valve clapper lifts and water moves through the pipes. Two devices sense that movement: the pressure switch on the alarm valve&#8217;s alarm line and the vane-type flow switch on the pipe. Both report to the <a href=\"\/en\/sa\/solutions\/fire-alarm-systems\/\">fire alarm panel<\/a>.<\/p>\n<p>A false alarm happens when water moves briefly for a reason other than an open sprinkler, or when a short pressure spike is enough to operate the device. The result is an unnecessary evacuation, disturbed occupants and lost trust in the system. The bigger risk is that building staff get used to the alarm and ignore it one day.<\/p>\n<p>This article covers waterflow signals on sprinkler systems only. For false alarms from smoke and heat detectors, see <a href=\"\/en\/sa\/media-center\/fire-alarm-false-alarms-causes\/\">causes of false alarms in fire alarm systems<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-c0287cd elementor-widget elementor-widget-text-editor\" data-id=\"c0287cd\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How do you find which device triggered the waterflow alarm?<\/h2>\n<p>Before touching any valve, read the panel event log. On an addressable panel the signal shows the module name and address, so you know whether it came from the pressure switch at the riser station or from a flow switch on a specific floor. The article on <a href=\"\/en\/sa\/media-center\/addressable-switch-monitor-sprinkler-flow-valve\/\">monitor modules for flow switches and valves<\/a> explains how these devices connect to the panel.<\/p>\n<div class=\"az-table-wrap\"><table>\n<thead><tr><th>Signal source<\/th><th>What it usually means<\/th><th>Check first<\/th><\/tr><\/thead>\n<tbody>\n<tr><td>Pressure switch on the alarm valve alarm line<\/td><td>The clapper lifted, or a surge reached the alarm line<\/td><td>Retard chamber and its bottom orifice, bypass line, system-side leaks<\/td><\/tr>\n<tr><td>Flow switch on one floor<\/td><td>Local water movement in that branch<\/td><td>Retard setting, trapped air, mounting position, vane condition<\/td><\/tr>\n<tr><td>All flow switches and the pressure switch together<\/td><td>A general pressure surge in the network<\/td><td>Fire pump or jockey pump starts, changes in supply pressure<\/td><\/tr>\n<tr><td>Alarm that repeats then clears<\/td><td>Trapped air or a small recurring leak<\/td><td>Venting air and finding leaks on the system side<\/td><\/tr>\n<\/tbody><\/table><\/div>\n<p>Log the time of every alarm. If it matches fire pump starts, or the hours when public supply pressure changes, the cause is most likely a surge and not a faulty device.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6dd86eb elementor-widget elementor-widget-text-editor\" data-id=\"6dd86eb\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>What causes a false waterflow alarm sprinkler problem?<\/h2>\n<h3>1. Pressure surges<\/h3>\n<p>A large pump starting or stopping, jockey pump cycling or a fluctuating supply all send a surge that moves water for a moment. The ACV-300 operation manual explains that a strong surge can lift the clapper briefly. A small amount of water then enters the retard chamber and drains before it reaches the water motor gong and pressure switch. With no retard chamber, or a clogged one, the signal goes straight through. To review the pumps themselves, see <a href=\"\/en\/sa\/media-center\/fire-pump-faults-troubleshooting\/\">fire pump faults and troubleshooting<\/a>.<\/p>\n<h3>2. Air trapped in the network<\/h3>\n<p>The ACV-300 datasheet notes that trapped air makes the clapper open and close repeatedly, which shows up as intermittent alarms. The stated fix is to purge the air and fit a vent valve on the system side and an air release valve at the end of the system. Potter&#8217;s VSR datasheet also lists trapped air as a cause of unintended operation.<\/p>\n<h3>3. Leaks on the system side<\/h3>\n<p>A visible or hidden leak downstream of the valve, or debris between the clapper and the seat, can cause an alarm without any sprinkler opening, according to the AFC operation manual. Look for a weeping sprinkler, a dripping joint or a drain valve that does not close fully.<\/p>\n<h3>4. Clogged retard chamber<\/h3>\n<p>The retard chamber has a bottom restriction orifice that drains it. If debris blocks it, water does not drain, the delay gets shorter and the alarm line sends a signal. The fix is to remove the chamber and flush the orifices.<\/p>\n<h3>5. Retard set to zero or too short<\/h3>\n<p>Some technicians set the flow switch retard to zero during testing and forget to reset it. After that, any brief water movement reaches the panel.<\/p>\n<h3>6. Flow switch installation errors<\/h3>\n<p>A switch too close to an elbow or valve, a vane rubbing the pipe wall, or a vane trimmed to fit the hole. The next section covers these.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-3a711f3 elementor-widget elementor-widget-text-editor\" data-id=\"3a711f3\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Setting the retard timer on the Potter VSR flow switch<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/potter-vsr-vane-type-waterflow-switch\/\">Potter VSR vane-type waterflow switch<\/a> is designed for wet sprinkler systems. Per Potter datasheet 5401146, its contacts operate when a flow of 10 GPM (38 LPM) or more occurs downstream of the device, and the flow must last long enough to overcome the selected retard period. The retard is pneumatic and recycles instantly once flow stops.<\/p>\n<div class=\"az-table-wrap\"><table>\n<thead><tr><th>Item<\/th><th>Datasheet value<\/th><\/tr><\/thead>\n<tbody>\n<tr><td>Retard range<\/td><td>0 to the maximum setting (60 to 90 seconds), set with a knob<\/td><\/tr>\n<tr><td>Minimum flow to operate<\/td><td>10 GPM (38 LPM)<\/td><\/tr>\n<tr><td>Flow sensitivity range for signal<\/td><td>4 to 10 GPM (15 to 38 LPM), UL<\/td><\/tr>\n<tr><td>Maximum surge<\/td><td>18 ft\/s (5.5 m\/s)<\/td><\/tr>\n<tr><td>Service pressure<\/td><td>450 PSI (31 bar), UL<\/td><\/tr>\n<tr><td>Contacts<\/td><td>Two SPDT (Form C)<\/td><\/tr>\n<tr><td>Sizes<\/td><td>2 in to 8 in (DN50 to DN200) depending on model<\/td><\/tr>\n<\/tbody><\/table><\/div>\n<p>Potter&#8217;s instructions say the time delay should be set at the minimum required to prevent false alarms. Turning the knob to maximum is not the fix, because a long delay also delays a real fire signal. Find what causes the surge, set the shortest delay that rides through it, then test.<\/p>\n<p>The delay allowed on a project comes from the approved design and the NFPA 72 edition accepted by the consultant and Civil Defense, so check it before changing the setting.<\/p>\n<h3>Installation rules that prevent false alarms<\/h3>\n<ul>\n<li>Do not install the switch within 6 in (15 cm) of a fitting that changes flow direction, or within 24 in (60 cm) of a valve or drain, per the datasheet.<\/li>\n<li>On horizontal pipe, mount it on the top of the pipe where it is accessible.<\/li>\n<li>The arrow on the saddle points in the direction of flow, because water operates the switch in one direction only.<\/li>\n<li>The vane must not rub the pipe or bind, and must never be trimmed. A trimmed paddle may stop the device from working and voids the warranty.<\/li>\n<li>Clean the pipe interior around the hole, and never drill into the switch base, since metal shavings can damage the electrical parts.<\/li>\n<li>Do not leave the cover off for long periods.<\/li>\n<\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-10179ac elementor-widget elementor-widget-text-editor\" data-id=\"10179ac\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Retard chamber and bypass line on the wet alarm check valve<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/american-afc-wet-alarm-check-valve-acv-300-series\/\">AFC ACV-300 wet alarm check valve<\/a> has three layers against false alarms according to its operation manual: a bypass line with a check valve that passes small fluctuations to the system side without lifting the clapper, a clapper design that stays shut under normal fluctuations, and the retard chamber that absorbs a strong surge. The delay is 5 to 60 seconds and the chamber drains in under 5 minutes.<\/p>\n<p>The datasheet separates variable pressure trim, used with a retard chamber, from constant pressure trim without one. If a system fed by automatically starting pumps, or by a supply with varying pressure, is fitted with constant pressure trim, false alarms should be expected. Full details of the models and trim are in the <a href=\"\/en\/sa\/media-center\/afc-acv-300-wet-alarm-check-valve\/\">ACV-300 wet alarm check valve<\/a> article.<\/p>\n<p>A useful site check: in normal condition the system-side gauge reads equal to or higher than the supply-side gauge, because the bypass check valve traps surges on the system side. If the system-side gauge keeps dropping, look for a leak.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-31c219b elementor-widget elementor-widget-text-editor\" data-id=\"31c219b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Step-by-step fix for a false waterflow alarm on site<\/h2>\n<ol>\n<li><strong>Notify the right people:<\/strong> the owner or safety officer, and the alarm receiving party if there is one, before any work on the system.<\/li>\n<li><strong>Read the panel log:<\/strong> identify the device, the time and how often it repeats.<\/li>\n<li><strong>Confirm there is no real flow:<\/strong> check the area for an open sprinkler or a leak before treating the alarm as false.<\/li>\n<li><strong>Bypass the zone at the panel:<\/strong> Potter&#8217;s instructions require the fire alarm zone or circuit for the switch to be bypassed before working on it. Do not block the trip stem or stop the vane from moving.<\/li>\n<li><strong>Check the retard:<\/strong> make sure the knob is not at zero, and set it at the minimum that prevents false alarms.<\/li>\n<li><strong>Check the valve station:<\/strong> flush the retard chamber orifice, confirm the bypass line and its check valve are sound, and compare the two gauges.<\/li>\n<li><strong>Vent the air:<\/strong> from the vent points and the ends of the system.<\/li>\n<li><strong>Test and restore:<\/strong> open the inspector&#8217;s test valve, confirm the signal arrives within the set delay, remove the bypass and record the result.<\/li>\n<\/ol>\n<p>If the switch leaks, Potter is clear: replace the detector. The retard and switch assembly, however, can be replaced in the field without draining the system or removing the switch from the pipe. The manufacturer gives a normal service life of 10 to 15 years for flow switches, which local conditions can shorten.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-31a13d3 elementor-widget elementor-widget-text-editor\" data-id=\"31a13d3\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Common mistakes that increase false waterflow alarms<\/h2>\n<div class=\"az-table-wrap\"><table>\n<thead><tr><th>Mistake<\/th><th>Effect<\/th><\/tr><\/thead>\n<tbody>\n<tr><td>Leaving the retard at zero after testing<\/td><td>Any short surge reaches the panel as an alarm<\/td><\/tr>\n<tr><td>Turning the retard to maximum to stop the alarms<\/td><td>A real fire signal is delayed and the cause remains<\/td><\/tr>\n<tr><td>Constant pressure trim with automatically starting pumps<\/td><td>No retard chamber to absorb surges<\/td><\/tr>\n<tr><td>Closing the alarm line valve to stop the gong<\/td><td>The real alarm is disabled too<\/td><\/tr>\n<tr><td>Flow switch near an elbow or valve<\/td><td>Turbulence moves the vane<\/td><\/tr>\n<tr><td>No test valve for the flow switch<\/td><td>The device cannot be tested, and Potter does not recommend using it in that case<\/td><\/tr>\n<\/tbody><\/table><\/div>\n<p>One more point from the datasheet: flow switches monitoring wet sprinkler systems must not be the sole initiating device to discharge foam, deluge or chemical suppression systems, because surges, trapped air or short retard times can cause unintended discharges.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-c3551e4 elementor-widget elementor-widget-text-editor\" data-id=\"c3551e4\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>When do you need a specialist inspection?<\/h2>\n<p>If alarms continue after resetting the retard and venting the air, or they match every pump start, the problem is usually in the design or the trim selection rather than in one device. A combined check of the riser station, the pumps and the control logic helps here. AZEIDK provides <a href=\"\/en\/sa\/services\/corrective-maintenance-technical-support\/\">corrective maintenance and technical support<\/a> for fire systems, and <a href=\"\/en\/sa\/services\/annual-maintenance-contracts\/\">annual maintenance contracts<\/a> that include periodic testing of flow switches and alarm valves.<\/p>\n<p>Potter recommends inspecting flow switches monthly for leaks and testing them quarterly or more often, in line with the applicable NFPA standards and the authority having jurisdiction.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-c9de4a9 elementor-widget elementor-widget-text-editor\" data-id=\"c9de4a9\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Frequently asked questions<\/h2>\n<div class=\"az-faq\">\n<details class=\"az-faq__item\"><summary><h3>Why does a flow switch alarm when no sprinkler has opened?<\/h3><\/summary><p>Usually because of a pressure surge from the fire pump or the supply, trapped air, or a retard set to zero or too short.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>What is the retard time on the Potter VSR?<\/h3><\/summary><p>It is adjustable from 0 to a maximum of 60 to 90 seconds per the datasheet, and should be set at the minimum that prevents false alarms.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>What does the retard chamber on a wet alarm valve do?<\/h3><\/summary><p>It takes the water that enters the alarm line during a short surge and drains it before it reaches the gong and pressure switch. On the ACV-300 the delay is 5 to 60 seconds per the operation manual.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Should I set the retard to maximum to stop false alarms?<\/h3><\/summary><p>No. A long delay also delays a real fire signal. Fix the cause of the surge first, then set the shortest delay that works, within what the approved design allows.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>How do I test a flow switch after the repair?<\/h3><\/summary><p>Open the inspector&#8217;s test valve. The switch needs at least 10 GPM (38 LPM) to operate. Then confirm the signal reaches the panel.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Can the VSR retard be replaced without draining the system?<\/h3><\/summary><p>Yes. Per Potter, the retard and switch assembly is field replaceable without draining the system or removing the switch, after the alarm circuit is bypassed at the panel.<\/p><\/details>\n<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-b819b28 elementor-widget elementor-widget-text-editor\" data-id=\"b819b28\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Conclusion<\/h2>\n<p>A false waterflow alarm on a sprinkler system has a traceable cause: a surge, air, a leak, a wrong retard setting or a poor installation. Start with the panel log to find the device, then check the alarm valve retard chamber, the flow switch retard and its mounting position. The rule stays the same: fix the cause, never disable the alarm.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-48fb165 elementor-widget elementor-widget-text-editor\" data-id=\"48fb165\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-cta\"><strong>Recurring waterflow alarms in your building?<\/strong> Send the panel log and photos of the riser station, and the AZEIDK team will review the cause and propose a fix. <a href=\"\/en\/sa\/contact\/\">Talk to the AZEIDK team<\/a><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-9faf5d4 elementor-widget elementor-widget-text-editor\" data-id=\"9faf5d4\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-source\"><strong>References:<\/strong> Potter Electric Signal Company: Model VSR Vane Type Waterflow Alarm Switch with Retard, datasheet 5401146 REV N, October 2021; <a href=\"\/en\/sa\/products\/potter-vsr-vane-type-waterflow-switch\/\" target=\"_blank\">AZEIDK: Potter VSR flow switch product page<\/a>; <a href=\"\/en\/sa\/media-center\/afc-acv-300-wet-alarm-check-valve\/\" target=\"_blank\">AZEIDK: AFC ACV-300 wet alarm check valve (based on the American Fire Control datasheet and operation manual)<\/a>.<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t","protected":false},"excerpt":{"rendered":"<p>False waterflow alarm sprinkler guide: surges, trapped air and leaks, the wet alarm valve retard chamber, and setting the Potter VSR flow switch retard timer.<\/p>\n","protected":false},"author":0,"featured_media":24906,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[221,323,322],"tags":[],"azeidk_region":[223],"class_list":["post-25111","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-azeidk-articles","category-systems-guides-en","category-systems-guides-ar"],"acf":[],"_links":{"self":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/25111","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/types\/post"}],"replies":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/comments?post=25111"}],"version-history":[{"count":1,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/25111\/revisions"}],"predecessor-version":[{"id":25713,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/25111\/revisions\/25713"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media\/24906"}],"wp:attachment":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media?parent=25111"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/categories?post=25111"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/tags?post=25111"},{"taxonomy":"azeidk_region","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/azeidk_region?post=25111"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}