{"id":18302,"date":"2026-11-23T13:55:28","date_gmt":"2026-11-23T10:55:28","guid":{"rendered":"https:\/\/azeidkgroup.com\/sa\/media-center\/"},"modified":"2026-11-23T13:55:28","modified_gmt":"2026-11-23T10:55:28","slug":"fire-water-tanks-egypt","status":"publish","type":"post","link":"https:\/\/azeidkgroup.com\/en\/eg\/media-center\/fire-water-tanks-egypt\/","title":{"rendered":"Fire Water Tanks: Capacity, Types and Design Basics"},"content":{"rendered":"\t\t<div data-elementor-type=\"wp-post\" data-elementor-id=\"18302\" class=\"elementor elementor-18302 elementor-18301 elementor-bc-flex-widget\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-8f1a449 e-con-full az-el-article e-flex e-con e-parent\" data-id=\"8f1a449\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-3b88e6c elementor-widget elementor-widget-text-editor\" data-id=\"3b88e6c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-intro\">A fire pump does not create water; it only moves it. On most Egyptian projects, the public water network alone cannot feed sprinklers and hose cabinets at the required flow and pressure for the full firefighting duration. That makes the <strong>fire water tank<\/strong> the source the whole system is built on. A mistake in its capacity or connections means a system that may stop before the fire does.<\/p>\n<p>This guide explains how to calculate the required capacity, the difference between gross and net capacity, tank types, the essential connections and fittings, and what NFPA 25 says about periodic inspection, with common design and site mistakes.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6187901 elementor-widget elementor-widget-text-editor\" data-id=\"6187901\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-keybox\"><h2>Key takeaways<\/h2><ul><li>Tank capacity equals the flow demanded by every system the tank feeds, multiplied by the required duration. It is not a fixed figure per building.<\/li><li>NFPA 13 links supply duration to hazard class, and references cite NFPA 14 as requiring at least 30 minutes for standpipe systems.<\/li><li>In a fire pump suction tank, net capacity is measured between the overflow inlet and the level of the anti-vortex plate, not from floor to roof.<\/li><li>An anti-vortex plate on the suction outlet stops air being drawn into the pump.<\/li><li>Regular checks of water level and of the tank interior are part of system maintenance, not a separate structural task.<\/li><\/ul><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-0ff37fd elementor-widget elementor-widget-text-editor\" data-id=\"0ff37fd\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>The Egyptian code and the technical standards<\/h2>\n<p>The binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026). Its second part covers mechanical firefighting systems. The General Directorate of Civil Protection (Ministry of Interior) reviews water supply and pump drawings as part of the project file. Industrial and storage facilities have their own requirements, so confirm the applicable Egyptian code with the designer and the authority.<\/p>\n<p>For technical details, NFPA standards serve as design references: NFPA 22 (2023 edition) for water tanks for private fire protection, NFPA 13 (2025 edition) for sprinkler demand and duration, NFPA 14 (2024 edition) for standpipe and hose systems, NFPA 20 (2025 edition) for fire pumps, and NFPA 25 (latest edition 2026) for tank inspection and maintenance. The figures here are guidance from these standards, not Egyptian legal requirements.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-2e0694c elementor-widget elementor-widget-text-editor\" data-id=\"2e0694c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How to calculate fire water tank capacity<\/h2>\n<p>The principle is simple: required net capacity = total demand flow \u00d7 duration. Each side of the equation needs care.<\/p>\n<h3>Demand flow<\/h3>\n<p>This is everything the system draws from the tank in the worst design case: the hydraulically calculated sprinkler demand for the design area, plus the hose stream allowance if hose cabinets or outside hydrants are fed from the same tank. The NFPA 13 annex explains that a tank feeding sprinklers only can be sized for the sprinkler demand, while a tank feeding sprinklers and hoses must cover the duration of all the equipment it supplies.<\/p>\n<h3>Duration<\/h3>\n<p>NFPA 13 links duration to hazard class. For hydraulically calculated systems, the table as MeyerFire reports it from the 2016 and 2019 editions gives 30 minutes for light hazard, 60 to 90 minutes for ordinary hazard, and longer for extra hazard; check the table in the 2025 edition adopted on your project. References cite NFPA 14 as requiring the supply for all three standpipe classes to meet system demand for at least 30 minutes. The final duration is set by the design, based on the occupancy, the Egyptian code and the authority.<\/p>\n<h3>Worked example (illustration only)<\/h3>\n<p>Assume the hydraulic calculation gives a sprinkler demand of 1,500 L\/min, the tank also feeds hose cabinets with an allowance of 950 L\/min, and the required duration is 60 minutes. Total flow is 2,450 L\/min, so net capacity is 2,450 \u00d7 60 = 147,000 litres, or about 147 m\u00b3. These figures are for illustration only; every project has its own calculation.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-8a4dc15 elementor-widget elementor-widget-text-editor\" data-id=\"8a4dc15\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Gross capacity and net capacity<\/h2>\n<p>Not all the water in a tank is usable. For suction tanks that feed fire pumps, NFPA 22 (2023 edition, as quoted by MeyerFire) measures net capacity between the overflow inlet and the level of the anti-vortex plate. For other tanks, it is measured between the overflow inlet and the discharge outlet. This means:<\/p>\n<ul><li><strong>Dead water:<\/strong> water below the suction level never reaches the pump, so it does not count.<\/li><li><strong>Space above the overflow:<\/strong> the gap between overflow level and tank roof does not count either.<\/li><li><strong>Extra margins:<\/strong> some designers add a little height above the suction to allow for sediment and level changes. This is design practice, not a requirement of the standard.<\/li><\/ul>\n<p>So the submittal should state net capacity, with the overflow and suction levels, not the tank&#8217;s outside dimensions.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-58e3586 elementor-widget elementor-widget-text-editor\" data-id=\"58e3586\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Types of fire water tanks<\/h2>\n<div class=\"az-table-wrap\"><table><thead><tr><th>Type<\/th><th>Description<\/th><th>What to check<\/th><\/tr><\/thead><tbody><tr><td>Concrete tank, at grade or underground<\/td><td>Built as part of the project structure, and may sit below or beside the pump room<\/td><td>Waterproofing, suction level relative to the pumps, access for cleaning<\/td><\/tr><tr><td>Bolted steel tank<\/td><td>Coated steel panels assembled on site<\/td><td>Corrosion protection, earthing and gaskets<\/td><\/tr><tr><td>Welded steel tank<\/td><td>Fabricated and welded on site for large capacities<\/td><td>Weld quality and internal and external coating<\/td><\/tr><tr><td>GRP \/ FRP sectional tank<\/td><td>Lightweight panels bolted together on site<\/td><td>UV and heat resistance, base supports<\/td><\/tr><tr><td>Elevated gravity tank<\/td><td>Gives pressure from elevation, without a pump<\/td><td>Structural loads and available pressure at the top floors<\/td><\/tr><tr><td>Pressure tank<\/td><td>A pressure vessel partly filled with water, the rest air<\/td><td>Limited capacity and pressure vessel requirements<\/td><\/tr><\/tbody><\/table><\/div>\n<p>A dedicated fire tank is the clearest option for design and approval. In a tank shared with domestic water, the fire reserve is usually kept by setting the domestic suction above the reserve level. Accept this only where the design and the authority approve it, and consider water quality and turnover.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-ea582ba elementor-widget elementor-widget-text-editor\" data-id=\"ea582ba\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Essential connections and fittings<\/h2>\n<ul><li><strong>Suction outlet and anti-vortex plate:<\/strong> when the tank is the suction source for a fire pump, its outlet needs a fitting that controls vortex flow. Kord Fire, citing NFPA 22, gives a plate diameter of at least twice the outlet diameter, and its installation guidance places the plate horizontally above the suction opening at about half the outlet diameter.<\/li><li><strong>Fill line and overflow:<\/strong> the overflow is sized larger than the fill line, so the tank cannot overfill, and discharges to a safe, visible point.<\/li><li><strong>Manholes and vents:<\/strong> one or two access manholes with sealed covers, and vents that prevent pressure or vacuum during filling and draw-down.<\/li><li><strong>Level gauge and low-level alarm:<\/strong> an easy-to-read level indicator, a supervised low-level alarm wired to the fire alarm panel, and a high-level alarm before overflow.<\/li><li><strong>Drain:<\/strong> to empty the tank for cleaning and internal inspection.<\/li><li><strong>Test return line:<\/strong> if the pump room returns pump test water to the tank, bring it in away from the suction so it does not disturb the flow.<\/li><\/ul>\n<p>The tank level relative to the pumps decides the pump type and suction arrangement. For suction piping inside the pump room, see our <a href=\"\/en\/eg\/media-center\/fire-pump-room-egypt\/\">fire pump room guide<\/a>. For flow and pressure selection, see our <a href=\"\/en\/eg\/media-center\/fire-pump-selection-egypt\/\">fire pump selection guide<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-1eb90c2 elementor-widget elementor-widget-text-editor\" data-id=\"1eb90c2\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Inspection and maintenance under NFPA 25<\/h2>\n<p>NFPA 25 sets an inspection programme for water storage tanks. The frequencies below are from Table 9.1.1.2 of the 2023 edition, as reproduced in NFPA&#8217;s official committee input report. The latest edition of the standard is 2026, so check the frequencies against it or the edition adopted on your project. They are technical guidance, not Egyptian law.<\/p>\n<div class=\"az-table-wrap\"><table><thead><tr><th>Item<\/th><th>NFPA 25 frequency (2023 edition)<\/th><\/tr><\/thead><tbody><tr><td>Water level, tank with supervised level alarm<\/td><td>Quarterly<\/td><\/tr><tr><td>Water level, tank without supervised alarm<\/td><td>Monthly<\/td><\/tr><tr><td>Exterior structure, supports, vents, foundation, ladders<\/td><td>Quarterly<\/td><\/tr><tr><td>Painted or insulated exterior surfaces and expansion joints<\/td><td>Annually<\/td><\/tr><tr><td>Interior of a steel tank without corrosion protection<\/td><td>Every 3 years<\/td><\/tr><tr><td>Interior of all other tank types<\/td><td>Every 5 years<\/td><\/tr><\/tbody><\/table><\/div>\n<p>Internal inspections often find sediment building up on the floor until it nears the anti-vortex plate, a damaged plate, wall corrosion or peeling coating, and a stuck float gauge that shows the tank full when it is less than half full.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-51b426c elementor-widget elementor-widget-text-editor\" data-id=\"51b426c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Common fire water tank mistakes<\/h2>\n<ul><li>Sizing the tank for sprinkler demand alone when it also feeds hose cabinets and hydrants.<\/li><li>Showing gross capacity in the submittal instead of net capacity.<\/li><li>Leaving out the anti-vortex plate, or fitting it at the wrong distance from the suction opening.<\/li><li>A tank shared with domestic water with no guarantee that the fire reserve is not drawn down in daily use.<\/li><li>An overflow smaller than the fill line, or with no visible outlet.<\/li><li>No low-level alarm to the fire alarm panel, so nobody knows the tank is empty.<\/li><li>No manhole and ladder to allow cleaning and internal inspection.<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-84b6d1b elementor-widget elementor-widget-text-editor\" data-id=\"84b6d1b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Tank and pumps: the full picture<\/h2>\n<p>The tank and the pumps work as one system: the pump&#8217;s rated flow sets how fast water is drawn, and the tank level sets the suction conditions. Within our <a href=\"\/en\/eg\/solutions\/fire-pump-systems-egypt\/\">fire pump solutions<\/a>, AZEIDK Egypt supplies complete <a href=\"\/en\/eg\/brands\/3pump\/\">3PUMP<\/a> sets: electric main pump, diesel standby pump and jockey pump with controllers on a common base. Duty points available in Egypt (Non-UL \/ non-listed) are 500 GPM at 8 bar, 750 GPM at 9 bar, 1000 GPM at 10 bar, 1500 GPM at 10 bar and 1500 GPM at 12 bar. UL\/FM-listed versions are manufactured and supplied on request.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-522b077 elementor-widget elementor-widget-text-editor\" data-id=\"522b077\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Frequently asked questions<\/h2><div class=\"az-faq\"><details class=\"az-faq__item\"><summary><h3>Is there a fixed fire tank size for each building?<\/h3><\/summary><p>No. Capacity is a calculation: the flow demanded by the systems the tank feeds, multiplied by the duration set by the design based on hazard class, the Egyptian code and the authority.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>Can one tank serve both fire and domestic water?<\/h3><\/summary><p>On some projects, yes, if the fire reserve is kept by a separate suction level and the design and authority approve it. A dedicated fire tank is clearer to design and inspect.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>What does an anti-vortex plate do?<\/h3><\/summary><p>It stops a vortex forming at the suction outlet and drawing air into the pump. That protects the pump from lost performance and cavitation, and lets water be used down to a level close to the outlet.<\/p><\/details><details class=\"az-faq__item\"><summary><h3>How often should the tank interior be inspected?<\/h3><\/summary><p>Under the NFPA 25 table in the 2023 edition: every 3 years for steel tanks without corrosion protection and every 5 years for other types, alongside the manufacturer&#8217;s instructions and the authority&#8217;s requirements.<\/p><\/details><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-517238e elementor-widget elementor-widget-text-editor\" data-id=\"517238e\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Conclusion<\/h2>\n<p>Fire water tank design starts with the calculation: which systems the tank feeds, their flow, and the required duration. Then set the net capacity between overflow and suction level, choose the tank type, and design the connections so water reaches the pump without air and its level is known at all times. After commissioning, regular inspection is the only proof that the calculated water is really there.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-e3d83ae elementor-widget elementor-widget-text-editor\" data-id=\"e3d83ae\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-cta\"><strong>Reviewing the fire tank and pump calculation on your project?<\/strong> Send us the sprinkler and hose demand and the required duration, and we will help you check the calculation and choose a suitable pump set. <a href=\"\/en\/eg\/contact\/\">Talk to the AZEIDK Egypt team<\/a><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-e25021d elementor-widget elementor-widget-text-editor\" data-id=\"e25021d\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-source\"><strong>References:<\/strong> <a href=\"https:\/\/webstore.ansi.org\/standards\/nfpa\/nfpa222023\" rel=\"noopener\" target=\"_blank\">NFPA 22-2023: Standard for Water Tanks for Private Fire Protection<\/a> (ANSI Webstore); <a href=\"https:\/\/www.meyerfire.com\/daily\/what-is-effective-capacity-of-water-storage-tank\" rel=\"noopener\" target=\"_blank\">What is the effective capacity of a water storage tank?<\/a> (MeyerFire); <a href=\"https:\/\/meyerfire.com\/daily\/tank-sizing-where-to-add-hose-allowance\" rel=\"noopener\" target=\"_blank\">Tank sizing: where to add hose allowance<\/a> (MeyerFire); <a href=\"https:\/\/kordfire.com\/anti-vortex-plate-specification-installation\/\" rel=\"noopener\" target=\"_blank\">Anti-vortex plate: specification and installation<\/a> (Kord Fire); <a href=\"https:\/\/docinfofiles.nfpa.org\/files\/AboutTheCodes\/25\/25_A2025_INM_AAA_FD_CIreport.pdf\" rel=\"noopener\" target=\"_blank\">NFPA 25 committee input report, A2025 cycle (Table 9.1.1.2)<\/a> (NFPA); <a href=\"https:\/\/webstore.ansi.org\/standards\/nfpa\/nfpa252026\" rel=\"noopener\" target=\"_blank\">NFPA 25-2026: Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems<\/a> (ANSI Webstore); <a href=\"https:\/\/www.meyerfire.com\/daily\/required-duration-for-secondary-water-supply\" rel=\"noopener\" target=\"_blank\">Required duration for secondary water supply<\/a> (MeyerFire); <a href=\"https:\/\/www.warrenforensics.com\/2024\/01\/29\/dive-into-suction-tank-issues-and-inspections\/\" rel=\"noopener\" target=\"_blank\">Dive into suction tank issues and inspections<\/a> (Warren Forensics)<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t","protected":false},"excerpt":{"rendered":"<p>Fire water tank guide for Egypt: sizing from flow and duration, net capacity and anti-vortex plates, tank types, and inspection under NFPA 22 and NFPA 25.<\/p>\n","protected":false},"author":0,"featured_media":26299,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[288],"tags":[],"azeidk_region":[226],"class_list":["post-18302","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-eg-engineering-guides"],"acf":[],"_links":{"self":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/18302","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/types\/post"}],"replies":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/comments?post=18302"}],"version-history":[{"count":2,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/18302\/revisions"}],"predecessor-version":[{"id":22957,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/18302\/revisions\/22957"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media\/26299"}],"wp:attachment":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media?parent=18302"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/categories?post=18302"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/tags?post=18302"},{"taxonomy":"azeidk_region","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/azeidk_region?post=18302"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}