Fire World FPLR Shielded Fire Alarm Cable, 14AWG, 16AWG and 18AWG

Fire World two-core FPLR shielded fire alarm cable with solid bare copper conductors, available in 14AWG, 16AWG and 18AWG.
العلامة التجارية
Fire-Alarm-Cable Fire World

تفاصيل المنتج

نظرة عامة على المنتج

The Fire World FPLR Shielded Fire Alarm Cable is designed for power-limited fire alarm circuits and features a two-core construction with a drain wire and shielding to help reduce electrical interference and support stable signal transmission.

The cable uses solid bare copper conductors with PVC insulation, a PET tape separator, a solid bare copper drain wire, PET/aluminium foil shielding and a red PVC outer sheath for clear identification within fire alarm installations.

The catalogue shows three available sizes:

• 18AWG — Ordering part number FPRL-UL18FW.
• 16AWG — Ordering part number FPRL-UL16FW.
• 14AWG — Ordering part number FPRL-UL14FW.

Key Features:

• FPLR fire alarm cable.
• Suitable for power-limited fire alarm circuits.
• Two-core construction.
• Solid bare copper conductors.
• Solid bare copper drain wire.
• PET/aluminium foil shielding.
• PET tape separator.
• PVC insulation.
• Red PVC outer sheath.
• Minimum insulation resistance of 200MΩ/km.
• Operating temperature up to 105°C.
• Minimum bend radius of eight times the cable diameter.
• Available in 14AWG, 16AWG and 18AWG.
• Compliant with UL1424 for FPLR riser cable.
• Associated with UL file E543704 according to the supplied documentation.

Size Details:

18AWG:
• Conductor diameter: 1.02mm.
• Insulation diameter: 1.42mm.
• Cable outer diameter: 4.2mm.
• Resistance: 22.4 ohm/km.
• Ordering part number: FPRL-UL18FW.

16AWG:
• Conductor diameter: 1.29mm.
• Insulation diameter: 1.69mm.
• Cable outer diameter: 4.8mm.
• Resistance: 14 ohm/km.
• Ordering part number: FPRL-UL16FW.

14AWG:
• Conductor diameter: 1.63mm.
• Insulation diameter: 2.03mm.
• Cable outer diameter: 5.5mm.
• Resistance: 8.8 ohm/km.
• Ordering part number: FPRL-UL14FW.

Standards and Compliance Shown in the Catalogue:

• UL1424 — FPLR Riser.
• UL2556.
• UL1666.
• IEC/EN 60332-1-2:2005+A1:2016+A11:2016+A12:2021.
• CPR Euroclass: Eca.
• EU CE Mark.
• RoHS.
• REACH.
• UL file number: E543704.

Important Note:

The supplied UL letter confirms that Fireworld UK Limited is associated with UL file E543704 under the Power-Limited Fire Alarm Cable category. The supplied product should still be checked for the authorised UL mark and the correct model designation, because the appearance of a company name in the UL database does not automatically certify every product manufactured by that company.

Brand: Fire World.
Available sizes: 14AWG, 16AWG and 18AWG.